What fiber connector types do you see, and what is the difference between UPC and APC?

Show the answer

Say this first

LC is the small duplex connector used on almost every SFP. SC is the older square push-pull connector, still common in patch panels and PON. ST is a legacy bayonet type. MPO or MTP carries 12 or 24 fibers in one ferrule for parallel optics like 40G and 100G SR4. UPC connectors are polished flat and are blue for single-mode. APC connectors are polished at 8 degrees to cut back-reflection, are green, and are used in PON and RF over fiber. Never mate APC with UPC.

Go deeper

Field rules

  • Inspect before you connect. Contamination is the most common cause of optical errors and loss. Use a fiber scope, clean with a proper cleaner, inspect again.
  • Polarity. Transmit on one end must meet receive on the other. Duplex patch cords are A to B. If a link stays down with both optics healthy, swapping the two strands at one end is a quick test.
  • MPO polarity follows TIA methods A, B and C. Mixing cassette and trunk types from different methods is a classic cause of dark links in new data center builds.
  • Bend radius. Tight bends leak light, especially at 1550 nm.

Why APC and UPC must not mix

The angled face of an APC does not sit flush against a flat UPC face. You get an air gap, high loss and possible damage to the end faces.

Traps

  • Thinking the connector color is cosmetic. Green APC and blue UPC look alike but must not mate.